• 36mm Hole 30A Split Core Current Transformer Outdoor Open Type Current Sensor with 30mA Output
  • 36mm Hole 30A Split Core Current Transformer Outdoor Open Type Current Sensor with 30mA Output
  • 36mm Hole 30A Split Core Current Transformer Outdoor Open Type Current Sensor with 30mA Output
  • 36mm Hole 30A Split Core Current Transformer Outdoor Open Type Current Sensor with 30mA Output
  • 36mm Hole 30A Split Core Current Transformer Outdoor Open Type Current Sensor with 30mA Output

36mm Hole 30A Split Core Current Transformer Outdoor Open Type Current Sensor with 30mA Output

Application: Electronic, Instrument
Type: Current Transformer
Phase: Single
Operation Condition: Outdoor
Usage: Measurement
Winding Form: Single Layer & Tightly Wound Type
Samples:
US$ 18/Piece 1 Piece(Min.Order)
| Request Sample
Customization:

Contact Supplier

Diamond Member Since 2018

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
ECS3630-1
Insulating Medium
Insulating Paper
Installation
Active Type
Magnetic Circuit Structure
Single Stage Type
Voltage Transformation Principle
Electromagnetic Type
Transport Package
60PCS/Box
Trademark
ECHUN
Origin
China
HS Code
8504500000
Production Capacity
1000PCS/Month

Product Description

36mm hole 30A split core current transformer outdoor open type current sensor with 30mA output

The ECS36-S series are outdoor split-core current transformers. The CT can be mounted to existing panels, such as control centers or load centers, to measure or monitor wattage. These CTs can be mounted without removing existing cables for easier installation

Customized current ratio available.

Rated Primary Current(Amp.) 50/60Hz

30nom(0.1~100A max)

Turn ratio

Np:Ns=1:1000

Current Ratio

30A/30mA


D.C. Resistance at 20 ºC
 
25(Ω)±10%

Accuracy@ RL=10Ω

1%


Phase Error at Rated Current Range
 
≤2.5°

Protection Level
 
7.5 Vo(Peak)

Operating Temperature Range

-40~70ºC

Storage Temperature Range

-45~85ºC

Dielectric Withstanding Voltage(Hi-pot)

4KV/1mA/1min


Impluse Withstand Voltage
 
5KV Peak

Insulation Resistance

DC500V/100MΩ min

Waterproof Level
IP65
 

Customized Current Ratio:


Model
 
Input Current Available Output

ECS36-100
 
100A CURRENT OUTPUTS @ 20mA,
33.3mA, 40mA,
50mA,100mA,1A, 5A
VOLTAGE OUTPUTS @ 0.25V,
0.333V, 0.5V, 1V, 2V

ECS36-200
 
200A

ECS36-300
 
300A

ECS36-400
 
400A

ECS36-500
 
500A

ECS36-600
 
600A

Applications:

Applications:
Current measurement
Monitoring and protection
Energy and sub-metering products
Network equipment
Instruments and sensors
Control systems

Advantage:
Mount easy.
Excellent linearity over the whole range.
Fully RoHS compliant.
Outdoor or Indoor use.
36mm Hole 30A Split Core Current Transformer Outdoor Open Type Current Sensor with 30mA Output

36mm Hole 30A Split Core Current Transformer Outdoor Open Type Current Sensor with 30mA Output

36mm Hole 30A Split Core Current Transformer Outdoor Open Type Current Sensor with 30mA Output
36mm Hole 30A Split Core Current Transformer Outdoor Open Type Current Sensor with 30mA Output
36mm Hole 30A Split Core Current Transformer Outdoor Open Type Current Sensor with 30mA Output
36mm Hole 30A Split Core Current Transformer Outdoor Open Type Current Sensor with 30mA Output 36mm Hole 30A Split Core Current Transformer Outdoor Open Type Current Sensor with 30mA Output
36mm Hole 30A Split Core Current Transformer Outdoor Open Type Current Sensor with 30mA Output

Send your message to this supplier

*From:
*To:
avatar Miss Kathy
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now